Installation, Calibration – Det-Tronics UD10 FlexVu Explosion-Proof Universal Display Unit User Manual

Page 66

Advertising
background image

4.2

95-8661

M-3

instAllAtion

wIRINg REQUIREmENTS
The simplest installation involves installing the sensor

into one of the UD10 openings and connecting the

wiring directly to the CGS interface board.

Sensor Separation
If the installation requires separation of the CGS sensor

and the UD10 Display, the sensor can be connected to

a model STB1 sensor termination box, and the CGS/

STB combination wired to the UD10.

In this case, shielded cable is recommended to help

protect against interference caused by extraneous

electrical “noise.”

In applications where the cable is installed in conduit,

the conduit should not be used for wiring to other

electrical equipment whenever possible. If other

equipment power wiring is run in the same conduit, the

cabling must be shielded.

The maximum allowable distance between the

CGS sensor and UD10 Display Unit is 500 feet, with

connecting cable 16 AWG minimum.

INSTAllATION AND wIRINg pROCEDURE
1. Determine the best mounting locations for the

detectors.

2. Install the CGS sensor within the proper opening in

the UD10 or STB junction box. Mount the device

with the sensor oriented vertically and the opening

pointing down. All junction boxes should be

electrically connected to earth ground.

3. Terminate all wiring at the proper terminals. Refer to

the appropriate illustration for details.

4. Double check that all wiring is the proper size and

type and has been installed correctly. Check for

correct operating voltage at the device.

noTe

Do not apply power to the system with the junction
box cover removed unless the area has been
de-classified.

5. Proceed with startup and calibration.

cAlibrAtion

To initiate calibration of the CGS sensor from the UD10

Display:

1. Using the magnet to activate the switches on the

UD10 display, navigate to the “Calibrate” menu.

Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test

Device Cal

Calibration
Cal Gas
Cal Gas Concentration
K Factor

Calibration

Execute

2. Activate “Execute” (Enter/Select) to start calibration.

3. The UD10 will display “Waiting for Zero” on the main

display screen as it performs zero calibration.

4. When zero calibration is complete, the UD10 will

display “Waiting for Gas” on the screen.

5. Apply calibration gas to the sensor.

6. The UD10 will display “Waiting for Span” on the

screen while the span calibration is being performed.

7. When the UD10 shows “Remove Cal Gas” on the

screen, remove the calibration gas from the sensor.

8. The UD10 automatically exits the Calibrate mode and

returns to normal operating mode upon completion

of a successful calibration.

UD10 mA Output During Calibration

(UD10 with CgS)

UD10 Display Reading

Standard

mode

Replicate

mode

Apply Zero Gas

3.8

2.2

Waiting for Gas

3.8

3.8

Waiting for Span

3.8

3.8

Remove Cal Gas

3.8

3.8

back to normal

4.0

4.0