SQM-242 Operating Manual

Three parameters are determined from the process reaction curve. They are the
steady state gain, K

p

, the dead time, L, and the time constant, T

1

. Several methods

have been proposed to extract the required parameters from the system response
as graphed in

Figure 9-7

. These are: a one point fit at 63.2% of the transition (one

time constant); a two point exponential fit; and a weighted least-square-exponential
fit. From the above information a process is sufficiently characterized so that a
controller algorithm may be customized.

Figure 9-7 Response of Process To An Open Loop Step Change

(At t=0 Control Signal is Increased)

A controller model used extensively is the PID type, shown in Laplace form in

equation [11]

.

[11]

Where

M(s) = manipulated variable or power

K

c

= controller gain (the proportional term)

T

i

= integral time

T

d

= derivative time

E(s) = process error

Figure 9-8

represents the controller algorithm and a process with first order lag plus

a dead time. The process block implicitly includes the dynamics of the measuring
devices and the final control elements, in our case the evaporator power supply.

M s

 

K

c

1

1

T

i

s

------- T

d

s

+

+

 Es

=