Table 5-7 Instance #2 (Poll or "COS/Cyclic Consuming")

#

Name

Access

Type

Comments

1

State

Get

USINT

0 = Nonexistent
1 = Configuring
2 = Waiting for Connections ID
3 = Established
4 = Timeout

2

Instance Type

Get

USINT

0000h (I/O Connection)

3

Transport Class Trigger

Get

BYTE

82h = Server, Polled, Class 2
80h = Server, COS/Cyclic, Class 0,
No Ack.
82h = Server, COS/Cyclic, Class 2, Ack.

4

Produced Connection ID

Get

UINT

FFFFh = Not Consuming (COS/Cyclic)
Other = CAN ID for transmission

5

Consumed Connection ID

Get

UINT

-

6

Initial Comm Characteristics

Get

BYTE

01h = Polled
- Produces over message, group 1
- Consumes over message, group 2
F1h = COS/Cyclic, No Ack.
- Consumes over message, group 2
01h = COS.Cyclic, Ack.
-Produces over message, group 1
- Consumes over message, group2

7

Produced Connection Size

Get

UINT

0000h = COS/Cyclic
other = Size of Fieldbus Input data (polled)

8

Consumed Connection Size

Get

UINT

Size of Fieldbus Output data

9

Expected Packet Rate

Get/Set(a)

UINT

-

12

Watchdog Timeout Action

Get/Set(a)

USINT

0000h (Transition to the timed out state)

13

Produced Connection Path Length

Get

UINT

0000h (COS/Cyclic)
0007h (Polled)

14

Produced Connection Path

Get

EPATH

No Value (COS/Cyclic)
20 04 25 64 00 30 03h (polled)

15

Consumed Connection Path
Length

Get

UINT

0007h

16

Consumed Connection Path

Get

EPATH

20 04 25 96 00 30 03h

17

Production Inhibit Time

Get

UINT

0000h