C13882 | monitoring time: watchdog, C13885 | clear process data, C13886 | set ext. diagnostic bit by – Lenze E84AYCPM User Manual

Page 100: C13885, C13882/1, C13886, C13882, C13882/2, 13 parameter reference

Advertising
background image

Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17

100

13

Parameter reference

13.1

Parameters of the communication module

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C13882

C13885

C13886

Parameter | Name:

C13882 | Monitoring time: Watchdog

Data type: UNSIGNED_32

Index: 10693

d

= 29C5

h

Display of the watchdog monitoring time determined by the PROFIBUS master

• A change in the watchdog monitoring time is immediately effective.

• Monitoring starts with the receipt of the first telegram.

• When a value of "0" is displayed, the monitoring function is deactivated.



Permanent interruption of PROFIBUS communication ( 81)

Display area

(min. value | unit | max. value)

0

ms

4294967295

Subcodes

Info

C13882/1

Watchdog monitoring time

C13882/2

DP-V1 MSC2

;

Read access … Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13885 | Clear process data

Data type: UNSIGNED_8

Index: 10690

d

= 29C2

h

Selection of the process data which the inverter will process in the event of a PROFIBUS failure in order to maintain

internal communication.
Selection list

(Lenze setting printed in bold)

0 Use of most recent master PDOs
1 PDOs are set to the value '0'

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13886 | Set ext. diagnostic bit by

Data type: BITFIELD_8

Index: 10689

d

= 29C1

h

Bit-coded selection of the error responses in the standard device causing the external diagnostic bit ("diag bit") to

be set (see PROFIBUS specification; bit 3 of byte 1 of the DP diagnostic messages).

• The diagnostic bit is sent to the PROFIBUS master where it is evaluated separately.

• The diagnostic bit is always set when a system error occurs.

• The Lenze setting "0" means that the diagnostic bit is not set for the following error responses.

• An advanced diagnostic message is always sent.

Value is bit-coded:

Bit 0 Error
Bit 1 Trouble
Bit 2 Quick stop by trouble
Bit 3 Warning locked
Bit 4 Warning
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT