4 error codes, Error codes, 9parameter data transfer – Lenze E84AYCPM User Manual

Page 74

Advertising
background image

Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17

74

9

Parameter data transfer

9.3

PROFIdrive parameter data channel (DP-V1)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.3.4

Error codes

Error code

Description

Explanation

Additional

information

0x0000

Impermissible parameter

number

Access to unavailable parameter

-

0x0001

Parameter value cannot be

changed

Change access to a parameter value that cannot be

changed

Subindex

0x0002

Lower or upper value limit

exceeded

Change access with value beyond the value limits

Subindex

0x0003

Faulty subindex

Access to unavailable subindex

Subindex

0x0004

No array

Access with subindex to non-indicated parameter

-

0x0005

Wrong data type

Change access with value that does not match the

data type of the parameter

-

0x0006

No setting permitted (only

resettable)

Change access with value unequal to 0 where this is

not permitted

Subindex

0x0007

Description element cannot

be changed

Change access to a description element that cannot

be changed

Subindex

0x0008

Reserved

(PROFIdrive profile V2: PPO-Write requested in the IR

is not available)

-

0x0009

Description data not

available

Access to unavailable description (parameter value is

available)

-

0x000A

Reserved

(PROFIdrive profile V2: Wrong access group)

-

0x000B

No parameter change rights Change access without parameter change rights

-

0x000C

Reserved

(PROFIdrive profile V2: Wrong password)

-

0x000D

Reserved

(PROFIdrive profile V2: Text in the cyclic traffic

cannot be read)

-

0x000E

Reserved

(PROFIdrive profile V2: Name in the cyclic traffic

cannot be read)

-

0x000F

No text array available

Access to unavailable text array (parameter value is

available)

-

0x0010

Reserved

(PROFIdrive profile V2: Missing PPO-Write)

-

0x0011

Request cannot be executed

due to the operating state

Access is not possible due to temporary reasons not

specified here

-

0x0012

Reserved

(PROFIdrive profile V2: Other error)

-

0x0013

Reserved

(PROFIdrive profile V2: date in the cyclic traffic

cannot be read)

-

0x0014

Value impermissible

Change access with the value that is inside the value

limits but not permissible for other permanent

reasons (parameters with defined individual values)

Subindex

0x0015

Response too long

The length of the current response exceeds the

maximum transmittable length

-

0x0016

Parameter address

impermissible

Impermissible or non-supported value for attribute,

number of subindices, parameter number, or

subindex, or a combination

-

0x0017

Format impermissible

Write request: Impermissible or non-supported

format of parameter data

-

0x0018

Number of values not

consistent

Write request: Number of values of the parameter

data do not match the number of subindices in the

parameter address

-

0x0019

Reserved

-

-

...
0x0064