Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17

32

6

Commissioning

6.3

Setting the station address

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.3

Setting the station address

[6-1]

DIP switch

The station addresses must differ from each other if several networked PROFIBUS stations are used.
The station address can be set via DIP switches 1 ... 64 or via the »Engineer« (code

C13899

).

The housing labelling indicates the valencies of the individual DIP switches for setting the station

address.

• Valid address range: 1 … 126 (max. 126 slave stations)

C13920

: Display of the current address setting of the switches

C13864

: Display of the station address active on the PROFIBUS

E84YCPM001G

The station address can be set via DIP switches 1 ... 64 or via the

»Engineer« (code

C13899

).

The unlabelled DIP switch (topmost position) does not have any

function.
Lenze setting: all switches in OFF position

Setting the station address via ...
DIP switch

C13899

Condition

At least one switch 1 … 64 = ON

• Switches 1 ... 64 = OFF

• All switches 1 ... 64 = ON

(invalid value "127")

DIP switch

64

32

16

8

4

2

1

Switch position

OFF

OFF

ON

OFF

ON

ON

ON

Value

0

0

16

0

4

2

1

Station address

= sum of the valencies = 16 + 4 + 2 + 1 = 23



DIP switch positions for setting the station address ( 107)

Note!

Switch off the voltage supply of the communication module and then on again in order

to activate changed settings.