1 bus cable specification, Bus cable specification, 5installation – Lenze E84AYCPM User Manual

Page 28

Advertising
background image

Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17

28

5

Installation

5.3

Activating the bus terminating resistor

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.3.1

Bus cable specification

Bus cable length
The length of the bus cable depends on the baud rate and cable type used. The data in the following

table applies to PROFIBUS cables of "FC-Standard Cable" cable type .

Tip!
We recommend taking the use of optical fibres into consideration for high baud rates.
Advantages of optical fibres:

• External electromagnetic interferences have no effect on the transmission path.
• Bus lengths of several kilometres are also possible with higher baud rates.
• The bus length is ...

• independent of the baud rate;
• dependent on the optical fibre used.

Note!

Only use cables which meet the listed specifications of the PROFIBUS user organisation.

Area

Values

Cable resistance

135 ... 165 Ω/km, (f = 3 ... 20 MHz)

Capacitance per unit length

30 nF/km

Loop resistance

< 110 Ω/km

Core diameter

> 0.64 mm

Core cross-section

> 0.34 mm

2

Cores

Twisted in pairs, insulated and shielded

Baud rate

Length

9.6 ... 93.75 kbps

1200 m

187.5 kbps

1000 m

500 kbps

400 m

1500 kbps

200 m

3000 ... 12000 kbps

100 m

Note!

The baud rate depending of the data volume, cycle time and number of stations should

only be selected as high as required for the application.