Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17

16

4

Technical data

4.2

Protective insulation

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.2

Protective insulation

Danger!

Dangerous voltage
If the Inverter Drives 8400 are used on a phase earthed mains with a rated mains voltage

400 V, protection against accidental contact is not ensured without implementing

external measures.
Possible consequences:
Death or severe injury
Protective measures:
If protection against accidental contact is required for the control terminals of the

inverter and the terminals of the plugged-in device modules, ...

• a double isolating distance must be provided.
• the components to be connected must be provided with a second isolating distance.

Note!

The existing protective insulation in the Inverter Drives 8400 is implemented according

to EN 61800-5-1.