6

Commissioning

6.2

Configuration of the controller (master)

31

Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.2

Configuration of the controller (master)

The controller (master) must be configured before communication with the communication

module is possible.

Configuration for the controller (master) and the DP-V0 parameter data channel
For configuring the PROFIBUS you must read the device description file of the communication

module into the master.
The device description file for the E84AYCPM communication module (PROFIBUS) can be found in

the Download area at:

www.Lenze.com

The following language variants of the device description file can be used:

• LENZ0A89.GSD (source file, English)
• LENZ0A89.GSG (German)
• LENZ0A89.GSE (English)

Defining the user data length
The user data length is defined during the initialisation phase of the master.
The Inverter Drives 8400 support the configuration of a maximum of 16 process data words (max.

32 bytes). The optional activation of the cyclic parameter data channel additionally occupies 4

process data word (8 bytes).
The user data lengths for process input data and process output data are the same.

Description of the device data base file

Example of selecting the device data base file

• "Drivecom-PAR (cons)" = DP-V0 parameter data channel (4 words)
• "PCD (8W cons)" = 8 process data words

Tip!
A detailed description of consistency is given in the chapter "

Consistent parameter data

"

( 80)

.

Selection text

Parameter data

with consistency

Process data

Assigned

IO memory

with consistency

without consistency

DRIVECOM-PAR

(cons) + PCD (nW

cons)

Yes

n words

-

4 + n words

PCD (nW cons)

-

n words

-

n words

PCD (nW)

-

-

4 words

4 words

n = 1 ... 16 process data words

DRIVECOM-PAR (cons) + PCD (8W cons)