C13880

C13881

Parameter | Name:

C13880 | Reaction on communication fault

Data type: UNSIGNED_8

Index: 10695

d

= 29C7

h

Monitoring response to a communication fault on the PROFIBUS

A change in the monitoring response is effective immediately.



Permanent interruption of PROFIBUS communication ( 81)

Selection list

0 No response
1 Error
3 Quick stop by trouble
4 Warning locked
6 Information

Subcodes

Lenze setting

Info

C13880/1

0: No response

The response set here for the "Watchdog/Data

Exchange" monitoring function is executed if the bus

station ...

• does not receive a message from the master within

the watchdog monitoring time (displayed in

C13882/

1

) if there is an active connection.

• detects that it is no longer in the "Data_Exchange"

status. Please see also the notes given under

C13881

.

C13880/2

0: No response

The response set here for the "DPV1 MSAC2" monitoring

is executed if the bus station does not receive any "DPV1

MSAC2" message from the master within the monitoring

time (displayed in

C13882/2

if there is an active

connection) and the MSAC2 connection is stopped by the

slave.

Note: We recommend only setting "information" as

response so that no drive-relevant response is executed.

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13881 | Monitoring time: Data exchange

Data type: UNSIGNED_16

Index: 10694

d

= 29C6

h

If the "Data Exchange" state is exited, the response parameterised under

C13880/1

is carried out when the

monitoring time for data exchange set here has expired.

• A value of "65535" in this code deactivates the monitoring function.

• A change in monitoring is effective immediately.

• The value set here for the monitoring time must be smaller than the watchdog monitoring time (

C13882/1

).



Permanent interruption of PROFIBUS communication ( 81)

Setting range

(min. value | unit | max. value)

Lenze setting

0

ms

65535 65535 ms

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT