3 settings and displays in the »engineer, Settings and displays in the »engineer, 10 monitoring – Lenze E84AYCPM User Manual

Page 83

Advertising
background image

10

Monitoring

10.3

Settings and displays in the »Engineer«

83

Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

10.3

Settings and displays in the »Engineer«

On the Monitoring tab of the »Engineer«, you can set or display the following parameters:

Parameter

Description

Reaction on communication

fault

(

C13880/1

)

The response set here takes place if the PROFIBUS station ...

• does not receive a message from the master within the watchdog

monitoring time (displayed in

C13882/1

) if there is an active connection;

• recognises that it is not in the "Data_Exchange" status anymore.

Please see also the information on

.

Clear process data

(

C13885

)

Selection of the process data which the inverter will process in the event of

a PROFIBUS failure in order to maintain internal communication.

The process data sent last by the master can be used or the process data can

be set to zero.

Monitoring time: Data

exchange

(

C13881

)

After the monitoring time set here has elapsed, the response set in

takes

place for the data exchange.

• The value "65535" deactivates the monitoring function.

• The monitoring time set here must be smaller than the watchdog

monitoring time

.

• A change in monitoring is effective immediately.



Permanent interruption of PROFIBUS communication ( 81)

Monitoring time: Watchdog

(

C13882/1

)

Display of the watchdog monitoring time determined by the PROFIBUS

master

• Monitoring starts with the receipt of the first telegram.

• When a value of "0" is displayed, the monitoring function is deactivated.

• A change in the watchdog monitoring time in the master is immediately

effective.



Permanent interruption of PROFIBUS communication ( 81)

Set ext. diagnostic bit upon

(

C13886

)

Bit-coded selection of the error responses in the standard device causing the

external diagnostic bit ("diag bit") to be set (see PROFIBUS specification; bit 3

of byte 1 of the DP diagnostic messages).

• The diagnostic bit is sent to the PROFIBUS master where it is evaluated

separately.

• The diagnostic bit is always set when a system error occurs.

• The Lenze setting "0" means that the diagnostic bit is not set for the

following error responses.

• An advanced diagnostic message is always sent.