9

Parameter data transfer

9.2

DRIVECOM parameter data channel (DP-V0)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.2.3

Byte 2: Subindex

Additional addressing via the subindex is required for those codes of the Inverter Drives 8400 that

contain a subcode (see code table).

9.2.4

Bytes 3 + 4: Index

The parameter (Lenze code) is selected via these two bytes according to the formula:

Index = 24575 - Lenze code number

(Also see "

Addressing of Lenze parameters

"

( 51)

)

Example:
The parameter C00105 (quick stop (QSP) deceleration time) is to be addressed:

• Index = 24575 - 105 = 24470 = 0x5F96
• The entries in bytes 3 + 4 for this example would be:

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

Service

Subindex

Index

High byte

Index

Low byte

Data 4 /

Error 4

Data 3 /

Error 3

Data 2 /

Error 2

Data 1 /

Error 1

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

Service

Subindex

Index

High byte

Index

Low byte

Data 4 /

Error 4

Data 3 /

Error 3

Data 2 /

Error 2

Data 1 /

Error 1

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

Service

Subindex

0x5F

0x96

Data 4 /

Error 4

Data 3 /

Error 3

Data 2 /

Error 2

Data 1 /

Error 1

Advertising