9parameter data transfer – Lenze E84AYCPM User Manual
Page 71

9
Parameter data transfer
9.3
PROFIdrive parameter data channel (DP-V1)
71
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Parameter format
Parameter value
Byte 11
Byte 12
Format
Number of values
Field
Data type
Values
Format
U8
0x02: Integer8
0x03: Integer16
0x04: Integer32
0x05: Unsigned8
0x06: Unsigned16
0x07: Unsigned32
0x09: Visible string
0x0A: Octet string
0x40: Zero
0x41: Byte
0x42: Word
0x43: Double word
Number of values
U8
0x01 or number of written subindices/parameters (with
several subindices/parameters only the parameter value
is repeated).
In the case of string codes, the number of characters is
entered here.
Byte 13
Byte 14
Byte 15
Byte 16
Value
Field
Data type
Values
Value
String
Any (length > 4 bytes possible)
U8
0x00 .... 0xFF
U16
0x0000 .... 0xFFFF
U32
0x0000 0000 .... 0xFFFF FFFF