Profibus watchdog: Monitoring time elapsed [0x01bc8130]

Profibus: Data_Exchange state exited [0x01bc8131]

Profibus watchdog: DP-V1 MSC2 monitoring time exceeded [0x01bc8132]

Response (Lenze setting printed in bold)

Setting:

C13880/1

(; Adjustable response)

:

None … System fault ; Fault … Trouble ; Quick stop by trouble ; Warning locked … Warning ; Information

Cause

Remedy

Permanent interruption of communication to the

PROFIBUS master.

Also see the chapter "

Permanent interruption of

PROFIBUS communication

"

( 81)

.

Check cables and terminals.

Response (Lenze setting printed in bold)

Setting:

C13880/1

(; Adjustable response)

:

None … System fault ; Fault … Trouble ; Quick stop by trouble ; Warning locked … Warning ; Information

Cause

Remedy

Data exchange via PROFIBUS has been stopped.

Also see the chapter "

Permanent interruption of

PROFIBUS communication

"

( 81)

.

Check cables and terminals.

The slave must receive new parameterisation and

configuration files from the master in order to be able to

exchange data again.

Response (Lenze setting printed in bold)

Setting:

C13880/2

(; Adjustable response)

:

None … System fault ; Fault … Trouble ; Quick stop by trouble ; Warning locked … Warning ; Information

Cause

Remedy

Permanent interruption of communication to C2-

PROFIBUS master.

Also see the chapter "

Permanent interruption of

PROFIBUS communication

"

( 81)

.

Check cables and terminals.