2 profibus connection, Profibus connection, Profibus connection ( 29) – Lenze E84AYCPM User Manual

Page 29: 5installation

Advertising
background image

5

Installation

5.3

Activating the bus terminating resistor

29

Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.3.2

PROFIBUS connection

The 9-pole Sub-D socket X201 serves to connect the communication module to the bus system.

Assignment of the 9-pin Sub-D socket X201

View

Pin

Assignment

Description

1

Not assigned

-

2

Not assigned

-

3

RxD/TxD-P

Data line B (received data/transmitted data, plus)

4

RTS

Request To Send (received data/transmitted data, no

differential signal)

5

M5V2

Data ground (ground to 5 V)

6

P5V2

5 V DC / 30 mA (bus termination)

7

Not assigned

-

8

RxD/TxD-N

Data line A (received data/transmitted data, minus)

9

Not assigned

-

1

6

5

9

Advertising