Technical data

Rated data

Controller for a mains voltage of 400 V / 500 V

3

l

73

EDKVF9338 DE/EN/FR 4.0

3.3.2

Controller for a mains voltage of 400 V / 500 V

Rated data at a mains voltage of 400 V

Basis of the data

Voltage

Frequency

Supply

3/PE AC 400 V

[U

N

]

340 V − 0 % ... 577 V + 0 %

45 Hz − 0 % ... 65 Hz + 0 %

DC 565 V (alternatively)

[U

DC

]

DC 480 V − 0 % ... 800 V + 0 %

˘

Output voltage

[U

OUT

]

3 ~ 0 ... U

N

0 ... 300 Hz

9300

Mains current

1)

Typical motor power

ASM (4−pole)

Power loss

Type

I

r

[A]

P

N

[kW]

P

N

[hp]

P

V

[kW]

EVF9335−EVVxxx

2)

200

110

150

2.8

EVF9336−EVVxxx

2)

238

132

200

3.3

EVF9337−EVVxxx

2)

285

160

250

4.0

EVF9338−EVVxxx

2)

356

200

300

5.0

1)

For a controller switching frequency of 2 kHz

2)

Device in variant V210, V240, V270 or V300

9300

Output currents

Rated current

Maximum current

2)

1 kHz

1)

2 kHz

1)

4 kHz

1)

1 kHz

1)

2 kHz

1)

4 kHz

1)

Type

I

N1

[A]

I

N2

[A]

I

N4

[A]

I

M1

[A]

I

M2

[A]

I

M4

[A]

EVF9335−EVVxxx

3)

210

210

210

315

315

315

EVF9336−EVVxxx

3)

250

250

250

375

375

375

EVF9337−EVVxxx

3)

300

300

270

450

450

405

EVF9338−EVVxxx

3)

375

375

330

560

560

495

Bold print = Lenze setting

1)

Switching frequency of the inverter

2)

The currents apply to a periodic load change with an overcurrent time of 1 minute at a maximum and a base load
time of 2 minutes with maximally 75 % I

Nx

3)

Device in variant V210, V240, V270 or V300