Electrical installation

Motor connection

Fan connection

5

l

87

EDKVF9338 DE/EN/FR 4.0

5.4

Motor connection

ƒ

To comply with the EMC regulations, Lenze recommends to use shielded motor
cables.

ƒ

Shield clamps are not included in the scope of supply.

(

Stop!

The user is responsible for sufficient strain relief!

BR2

BR1

PE U

V

W

40 mm

PE

15-20 Nm

M6

133-176 lb-in

U, V, W

25-30 Nm

M8

221-264 lb-in

0

max.

300 mm

1

9300VEC005

Fig. 5−6

Motor connection example

BR1, BR2

The brake resistor can only be operated with the variants V060, V110, V270 and V300
For connection see the 9300 vector System Manual

0

Connect the motor cable shield with a surface as large as possible to the control
cabinet mounting plate by using the clamps.

1

Conductive surface

Ensure to have the poles right!
Do not exceed the maximum motor cable length!

Cable cross−sections for the motor connection

Type

Installation to EN 60204−1

U, V, W [mm

2

]

PE [mm

2

]

EVF9335−EV
EVF9335−EVVxxx

150

2 × 50

1)

95

EVF9336−EV
EVF9336−EVVxxx

150

2 × 50

1)

95

EVF9337−EV
EVF9337−EVVxxx

150

2 × 50

1)

95

EVF9338−EV
EVF9338−EVVxxx

240

2 × 95

1)

150

1)

Multiple conductor; both conductors must have the same cross−section

Observe the national and regional legislation