Electrical installation

Supply and fan connection at the controller for a mains voltage of 400 V/500V
Connection to the DC bus (+UG, −UG)

5

l

84

EDKVF9338 DE/EN/FR 4.0

5.3.2

Connection to the DC bus (+U

G

, −U

G

)

ƒ

For compliance with EMC requirements, Lenze recommends to use shielded DC−bus
cables.

ƒ

Shield clamps are not included in the scope of supply.

BR2

BR1

+UG -UG

PE U

V

W

L1

101 102 103 104

L2 L3 PE

40 mm

PE

15-20 Nm

M6

133-176 lb-in

+U

G

-U

G

25-30 Nm

M8

221-264 lb-in

max.

300 mm

1

0

9300VEC074

Fig. 5−4

Connection example to +U

G

and −U

G

BR1, BR2

Brake resistors can only be operated with variants V270 and V300
For connection see the 9300 vector System Manual

0

Connect the DC−bus cable shield to the conductive control cabinet mounting plate with
a contact surface as large as possible by using the shield clamps.

1

Conductive surface

Ensure to have the poles right!

Fuses and cable cross−sections for DC−bus connection

Type

Installation to EN 60204−1

Fuse

2)

+U

G

, −U

G

[mm

2

]

PE [mm

2

]

EVF9335−EVV210
EVF9335−EVV240
EVF9335−EVV270
EVF9335−EVV300

315A

150

2 × 50

1)

95

EVF9336−EVV210
EVF9336−EVV240
EVF9336−EVV270
EVF9336−EVV300

350 A

150

2 × 50

1)

95

EVF9337−EVV210
EVF9337−EVV240
EVF9337−EVV270
EVF9337−EVV300

400 A

240

2 × 95

1)

95

EVF9338−EVV210
EVF9338−EVV240
EVF9338−EVV270
EVF9338−EVV300

500 A

240

2 × 95

1)

150

1)

Multiple conductor; both conductors must have the same cross−section

2)

Only use fuses of the gRL utilisation category

Observe the national and regional legislation