Electrical installation – Lenze EVF9338 User Manual

Page 89

Advertising
background image

Electrical installation

Motor connection

Wiring of motor temperature monitoring

5

l

89

EDKVF9338 DE/EN/FR 4.0

Characteristics of the connection for motor temperature monitoring:

Terminals T1, T2

Connection

l

PTC thermistor
– PTC thermistor with defined tripping temperature (acc. to DIN 44081 and

DIN 44082)

l

Thermal contact (NC contact)
– Thermostat as NC contact

Tripping point

l

Fixed (depending on the PTC/thermal contact)

l

PTC: R

J

>

1600

W

l

Configurable as warning or error (TRIP)

Notes

l

Monitoring is not active in the Lenze setting.

l

If you do not use a Lenze motor, we recommend the use of a PTC thermistor up
to 150°C.

Motor with KTY thermal sensor

)

Note!

ƒ

We recommend to use Lenze system cables for wiring.

ƒ

For self−made cables only use cables with shielded cores twisted in pairs.

PE U V W

T1 T2

+UG -UG

PES

PES

PE

M

3~

PES

PES

KTY

X8/5

X8/8

PES

X8

X9

X10

9300vec121

Fig. 5−8

Connection of KTY thermal sensor at incremental encoder input X8

Characteristics of the connection for motor temperature monitoring:

Pins X8/5, X8/8 of incremental encoder input (X8)

Connection

Linear KTY thermal sensor

Tripping point

l

Warning: Adjustable

l

Error (TRIP): Fixed at 150 °C

Notes

l

Monitoring is not active in the Lenze setting.

l

The KTY thermal sensor is monitored with regard to interruption and short
circuit.