Electrical installation

Control terminals

With function "Safe torque off" deactivated

5

l

95

EDKVF9338 DE/EN/FR 4.0

5.5.3

With function "Safe torque off" deactivated

)

Note!

If the function "Safe torque off" is not made use of, the safety relay K

SR

must

be energised permanently to ensure the tension supply of the power output
stage.

Supply via internal voltage source

ƒ

If a freely assignable digital output (e.g. X5/A1) is assigned permanently to HIGH
level, it serves as an internal voltage source. Every output has a maximum load
capacity of 50 mA.
– The relay K

SR

and two digital inputs (X5/28 and e.g. X5/E1) can be supplied with

voltage via a digital output.

– Two digital outputs must be connected in parallel and assigned permanently to

HIGH level in order to obtain the maximum wiring (relays K

SR

and X5/E1 ... X5/E5,

X5/ST1).

ƒ

For the supply of the analog inputs (X6/1, X6/2 and X6/3, X6/4) you have to set a
freely assignable analog output (e. g. X6/63) permanently to HIGH level.

GND2

+24V

+5 V

E5

A2 A3 A4 ST1ST2 59

39

3k

47k

50mA

50mA

50mA

50mA

X5 28 E1 E2 E3 E4

3k

3k

3k

3k

3k

X11 K31K32 33 34

S1

+

K

SR

A1

X3

X6

1

2

3

4

242R

1
2
3
4
5
6

100k

100k

100k

100k

3.3nF

GND1

GND1

7

7

62 63

AIN1

AIN2

AOUTx

AOUT2

AOUT1

1

3

2

4

7

10k

10k

9300vec0137

Fig. 5−12

Wiring of digital and analog inputs/outputs with function "Safe torque off" deactivated, given an
internal voltage source

S1

Controller enable
NO contact or NC contact

Z

Load
Minimum wiring required for operation

Terminal assignment in the Lenze setting:

^ 97