Electrical installation

Supply and fan connection at the controller for a mains voltage of 400 V/500V

Fan connection

5

l

85

EDKVF9338 DE/EN/FR 4.0

5.3.3

Fan connection

Fan connection when controller is supplied with mains voltage

Lay a bridge between the terminals when a controller is operated on a mains.

AC 340 ... 440 V

AC 440 ... 577 V

(when being delivered)

L1 L2

101 102 103 104

101 102 103 104

L1 L2

9300vec044

9300vec045

Fan connection when controller is supplied via the DC bus

{

Danger!

When the fan is externally supplied with voltage, the terminal L2 carries
dangerous mains voltage!

When the controller is supplied via the DC bus, the fan must be separately supplied with
mains voltage (see

1). In this case, the bridge between the terminals 102 and 103 must be

removed (see

0).

Remove bridge

Mains connection for the operation of the fan on

AC 340 ... 440 V

AC 440 ... 577 V

101 102 103 104

}

0

L1 L2

AC 340 … 440 V

101 102 103 104

1

L1 L2

AC 440 … 577 V

101 102 103 104

1

L1 L2

9300vec160

9300vec046

9300vec047