Electrical installation

Controller mains connection for a mains voltage of 400 V

5

l

82

EDKVF9338 DE/EN/FR 4.0

5.2

Controller mains connection for a mains voltage of 400 V

(

Stop!

The user is responsible for sufficient strain relief!

BR2

BR1

PE U

V

W

L1 L2 L3 PE

L1, L2,

L3

25-30 Nm

M8

221-264 lb-in

PE

15-20 Nm

M6

133-176 lb-in

40 mm

9300VEC003

Fig. 5−2

Mains connection example

BR1, BR2

Brake resistors can only be operated with variants V060 and V110
For connection see the 9300 vector System Manual

Fuses and cable cross−sections for the mains supply

Type

Installation to EN 60204−1

Fuse

2)

L1, L2, L3 [mm

2

]

PE [mm

2

]

EVF9335−EV
EVF9335−EVV030
EVF9335−EVV060
EVF9335−EVV110

250 A

150

2 × 50

1)

95

EVF9336−EV
EVF9336−EVV030
EVF9336−EVV060
EVF9336−EVV110

315A

150

2 × 50

1)

95

EVF9337−EV
EVF9337−EVV030
EVF9337−EVV060
EVF9337−EVV110

315A

150

2 × 50

1)

95

EVF9338−EV
EVF9338−EVV030
EVF9338−EVV060
EVF9338−EVV110

400 A

240

2 × 95

1)

150

1)

Multiple conductor; both conductors must have the same cross−section

2)

Lenze recommends to use fuses of the gRL utilisation category

Observe the national and regional legislation