Electrical installation

Supply and fan connection at the controller for a mains voltage of 400 V/500V

Mains connection

5

l

83

EDKVF9338 DE/EN/FR 4.0

5.3

Supply and fan connection at the controller for a mains voltage of 400 V/500V

(

Stop!

The user is responsible for sufficient strain relief!

5.3.1

Mains connection

BR2

BR1

+UG -UG

PE U

V

W

L1

101 102 103 104

L2 L3 PE

L1, L2,

L3

25-30 Nm

M8

221-264 lb-in

PE

15-20 Nm

M6

133-176 lb-in

40 mm

9300VEC032

Fig. 5−3

Mains connection example

BR1, BR2

Brake resistors can only be operated with variants V270 and V300
For connection see the 9300 vector System Manual

Fuses and cable cross−sections for the mains supply

Type

Installation to EN 60204−1

Fuse

2)

L1, L2, L3 [mm

2

]

PE [mm

2

]

EVF9335−EVV210
EVF9335−EVV240
EVF9335−EVV270
EVF9335−EVV300

250 A

150

2 × 50

1)

95

EVF9336−EVV210
EVF9336−EVV240
EVF9336−EVV270
EVF9336−EVV300

315A

150

2 × 50

1)

95

EVF9337−EVV210
EVF9337−EVV240
EVF9337−EVV270
EVF9337−EVV300

315A

150

2 × 50

1)

95

EVF9338−EVV210
EVF9338−EVV240
EVF9338−EVV270
EVF9338−EVV300

400 A

240

2 × 95

1)

150

1)

Multiple conductor; both conductors must have the same cross−section

2)

Lenze recommends to use fuses of the gRL utilisation category

Observe the national and regional legislation