1 calling the boot monitor in the control system, Calling the boot monitor in the control system – Lenze ETC Motion Control User Manual
Page 83

Getting started
Updating the firmware of the ETCHx in the "Standalone" operating mode
Calling the boot monitor in the control system
2.16
2.16.1
l
83
EDSTCXN EN 2.0
2.16
Updating the firmware of the ETCHx in the "Standalone" operating mode
)
Note!
The steps described in this chapter only apply to the ETCHx
variant (DIN rail variant); they are not required for the ETCPx
variant (PCI card).
2.16.1
Calling the boot monitor in the control system
Initial state: The communication between PC and ETCHx has been
established and the monitor interface activated (
¶ 21)
1. In the terminal program, enter the command reboot.
2. During the running reboot process, press and hold the <Shift> + <!>
keys.
ETCM012
When the prompt ">" appears, the input in the boot monitor of the
control system is active. On the control system, the LEDs 1 ... 6 flash
circulatingly.
)
Note!
When the firmware is running, the control system can also be
reset by switching the control system on/off or by pressing the
reset key.