Appendix E Data Scales

134

Series PM172 Powermeters

Appendix E Data Scales

The maximum values for volts, amps and power in the PM172 setup and in
communications are limited by the voltage and current scale settings. See

Device Options

in Chapter 4 on how to change the voltage scale in your

meter.

The following table defines the meter data scales.

Scale Conditions

Range

Maximum voltage
(V max)

All configurations

Voltage scale

× PT Ratio, V

1

Maximum current
(I max)

All configurations

Current scale

× CT Ratio, A

2, 3

Wiring 4LN3, 3LN3, 3BLN3

V max

× I max × 3, W

Maximum Power
(P max)

4

Wiring 4LL3, 3LL3, 3BLL3,

3OP2, 3OP3, 3DIR2

V max

× I max × 2, W

25, 50 or 60 Hz

100 Hz

Maximum
frequency

400Hz 500

Hz

1

The default voltage scale is 144V. The recommended voltage scale is

120V+20% = 144V for using with external PT’s, and 690V+20% = 828V for
a direct connection to power line.

2

CT Ratio = CT primary current/CT secondary current

3

The default current scale is 2

× CT secondary (2.0A with 1A secondaries and

10.0A with 5A secondaries)

.

4

Maximum power is rounded to whole kilowatts. With PT=1.0, it is limited to

9,999,000 W.