Transformer correction, Chapter 3 display operations menu operations, Series pm172 powermeters – SATEC RDM172 Manual User Manual

Page 44

Advertising
background image

Chapter 3 Display Operations

Menu Operations

44

Series PM172 Powermeters

The following table lists available options.

Label Parameter

Options

Default

Description

P.cAL Power

calculation
mode

rEAc (reactive power),
nAct (non-active

power)

Reactive

The method used for
calculating reactive and
apparent powers

roLL Energy

roll

value

E

10.E4=10,000
10.E5=100,000
10.E6=1,000,000
10.E7=10,000,000
10.E8=100,000,000
10.E9=1,000,000,000

10.E9

The value at which
energy counters roll
over to zero

Ph.En Phase

energy

option

E

diS = disabled
En = enabled

Disabled

Enables phase energy

calculations

Hr.En Harmonic

energy option

EH

diS = disabled
En = enabled

Disabled Enables

harmonic

energy calculations

bAtt Backup

battery

mode

OFF = switched OFF
On = switched ON

OFF

Allows to conserve a
battery while the meter
is out of operation

tESt Energy

test

mode

E

OFF = disabled

Ac.Ei = Wh pulses
rE.Ei = varh pulses

Disabled

Setting this option puts

the meter into the
energy test mode

An.EP Analog

expander
option

1

nonE = disabled
0-20 = 0-20 mA
4-20 = 4-20 mA
0-1 = 0-1 mA
-1-1 = ±1 mA

Disabled

Enables outputs for the
AX-8 analog expanders
through port COM2. See
“Analog Expander

Setup”

C.Str Starting

Current, %FS

0.1-2.0

0.1%FS

Specifies the low
current measurement
limit in percent of the
full scale current (1A,

5A). Available in the
PM172P/E V13.1.19 and
later.

1

Do not enable the analog expander output if you do not have the analog expander

connected to the meter, otherwise it will disturb the computer communications.

Transformer Correction

This menu is available in the PM172P/E with firmware V13.1.19 and later, or
V13.71.12 and later.

Transformer correction allows you to compensate ratio and phase angle

inaccuracies of the user voltage and current instrument transformers. To
enter the menu, select the “t.Cor” entry from the Main menu, and then press
the ENTER button.

To select a setup option:

1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to scroll to the

desired option.

To change the option:

1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the

desired option.

3. Press ENTER to confirm your changes and to store your

new setting, or press ESC to discard changes.

To exit the menu, press ESC.