Chapter 4 PAS Application Software Configuring

Recorders

Series PM172 Powermeters

89

automatically update the “Parameter” box with the

following parameter in the group.

8. Add the name for your data log file in the “Name” box. It

will appear in the data log reports.

9. Save your new setup to the device database, and send it

to the meter.

Factory Preset Periodic Data Logs

Data logs #1 and #2 are factory preset for periodic recording of the standard
power quantities as shown in the following table.

No. Parameter No. Parameter

Data Log #1

1 V1/V12

9 Total

kVA

2 V2/V23

10 Total

PF

3 V3/V31

11 V1/V12

THD

4 I1

12 V2/V23

THD

5 I2

13 V3/V31

THD

6 I3

14 I1

THD

7

Total kW

15

I2 THD

8

Total kvar

16

I3 THD

Data Log #2

1

V1/V12 Demand

9

KVA Sliding Demand

2

V2/V23 Demand

10

kWh Import

3

V3/V31 Demand

11

kWh Export

4

I1 Demand

12

kvarh Import

5

I2 Demand

13

kvarh Export

6 I3

Demand

14 kVAh

7

kW Import Sliding Demand

15

In

8

kvar Import Sliding Demand

16

Frequency

TOU Profile Data Log Files

Data Log #8 is configurable to store TOU daily profile log records on a daily
basis.

A TOU profile log file is organized as a multi-section file that has a separate
section for each TOU energy and maximum demand register. The number of

sections is taken automatically from the Summary/TOU Registers setup (see
“Configuring Summary and TOU Registers”). If you selected to profile TOU