Load bar graph, Energy pulse led, Port activity leds – SATEC RDM172 Manual User Manual

Page 33: Navigation buttons, Data display, Display features, Measurement units

Advertising
background image

Chapter 3 Display Operations

Data Display

Series PM172 Powermeters

33

numeric LED display shows up to three parameters at a time. Small

rectangular or triangular LEDs at right and below the display indicate the
displayed parameters and their measurement units.

The display layout may change depending on the meter type and mode of
operation. There are three modes of display operation: data display, status
display, and programming mode display.

Load Bar Graph

The load bar graph displays the amount, in percent (40% to 110%), of the
present current load with respect to user-defined nominal load current. The

reference nominal current can be set up in amps through the Display Setup
menu. If it is set to 0 (default), the current load is referenced to the specified
CT primary current.

Energy Pulse LED

The PM172E and PM172EH have a red “Energy Pulse” LED. It flashes at a
constant rate when a load is applied to the meter. There are two modes of
LED operation: normal and test. In normal mode, the LED pulses indicate
imported Wh at a rate of 1,000 pulses per kWh in secondary units. In test

mode, the LED pulses indicate either imported Wh, or imported (inductive)
varh at a rate of 10,000 pulses per kWh/kvarh. The energy test mode can be
enabled through the Display Setup menu. When in test mode, the energy
and demand accumulators do not account for consumed energy.

Port Activity LEDs

The meter has two yellow LEDs “COM1” and “COM2”, which indicate activity
on the two communication ports. The port’s LED flashes when the port is

receiving or transmitting data. With the Ethernet or Profibus option, the
“COM1” LED flashes constantly regardless of the port activity.

When the display module is connected remotely through a 3-wire RS-485
interface, the “COM1” LED indicates the display port activity, while the
“COM2” LED is not operational.

Navigation Buttons

The PM172 is provided with six push buttons that are normally used to
navigate between different measurement displays. In programming mode,

the buttons access the device setup menus and the default factory-set
device settings can be changed.

Data Display

In data mode, the display is normally updated once per second; you can
adjust the display update rate via the Display Setup menu.

Display Features

Measurement Units

Currents are always displayed in amperes with two decimal places.

Measurement units for voltage and power depend on the connection scheme
of the meter:

• When direct wiring is used, voltages are displayed in

volts with one decimal place, and power in kilowatts
with three decimal places.

Advertising