Configuring dnp3, Dnp options, Configuring communication protocols – SATEC RDM172 Manual User Manual

Page 94: Configuring modbus

Advertising
background image

Chapter 4 PAS Application Software

Configuring Communication Protocols

94

Series PM172 Powermeters

Configuring DNP3

DNP Options can be changed both via DNP3 and Modbus. Refer to the
PM172 DNP3 Reference guide for information on the protocol
implementation and a list of the available data points.

DNP Options

To view or change the factory-set DNP options, select Protocol Setup from
the Meter Setup menu and click on the DNP Options tab.

The following table describes available DNP options. Refer to the DNP3
Data Object Library document available from the DNP User’s Group on the
DNP3 object types.

Parameter Options Default

Description

Binary Inputs (BI)

Number of BI to

Generate events

0-64

3

0

The total number of BI change event

points for monitoring

Binary Input
Object

Single-bit
With Status

Single-bit

The default BI object variation for
requests with qualifier code 06 when no
specific variation is requested

Binary Input

Change Event
Object

Without Time
With Time

With Time

The default BI change event object

variation for requests with qualifier code
06 when no specific variation is
requested

Analog Inputs (AI)

Number of AI to

Generate events

0-64

3

32

The total number of AI change event

points for monitoring

Analog Input

Object

32-bit

32-bit –Flag
16-bit
16-bit –Flag

16-bit -Flag

The default AI object variation for

requests with qualifier code 06 when no
specific variation is requested