background image

Chapter 3 Display Operations

Menu Operations

Series PM172 Powermeters

55

Label Option Format/Range

Description

dSt Daylight

saving

time option

diS = disabled
En = enabled

When DST is disabled, the RTC operates
in standard time only. When enabled, the
device automatically updates the time at
2:00 AM at the pre-defined DST switch
dates.

dSt.S

DST start date

Month-week-
weekday
Week = 1

st

, 2

nd

, 3

rd

,

4

th

or LSt (last week

of the month)

The date when Daylight Saving Time
begins. The DST switch point is specified
by the month, week of the month and
weekday. By default, DST starts at 2:00
AM on the second Sunday in March of
each year.

dSt.E

DST end date

Month-week-
weekday
Week = 1

st

, 2

nd

, 3

rd

,

4

th

or LSt (last week

of the month)

The date when Daylight Saving Time
ends. The DST switch point is specified by
the month, week of the month and
weekday. By default, DST ends at 2:00
AM on the first Sunday in November of
each year.

dSt.S
Hour

DST start hour

1-6

The time when Daylight Saving Time
begins.

dSt.E
Hour

DST end hour

1-6

The time when Daylight Saving Time
ends.

Resetting Accumulators and Maximum Demands

To enter the menu, select the “rst” entry from the Main menu, and then press
the ENTER button.

The Reset menu allows you to separately reset minimum/maximum log
records, maximum demands and counters.

To reset the desired registers:

1. Highlight the middle window by pressing briefly the

SELECT button.

2. Select the desired entry by scrolling through the list with

the UP and DOWN arrow buttons until the desired entry

appears.

3. Press the SELECT button briefly to highlight the lower

item.

4. Press and hold the ENTER button for 5 seconds.
5. Release the button. The “do” entry is replaced with “done”

showing the operation is complete.

The following table shows available options.

Label Description

Lo.Hi

Clears Min/Max log

A.dnd

Clears maximum ampere, volt and harmonic demands

P.dnd

Clears maximum power demands

dnd

Clears all maximum demands

Enr

Clears all total energies

tOU.d

Clears summary and TOU maximum demands

tOU.E

Clears summary and TOU energy registers

Cnt

Clears all counters

Cnt1 – Cnt4 Clears counter #1-#4

rSt

do

Lo.Hi

Advertising