Chapter 4 PAS Application Software

General Meter Setup

68

Series PM172 Powermeters

Parameter Options

Default Description

Phase Angle Error,
minutes

-600 to 600
(-2700 to 2700 with
V13.7X.XX)

0

The phase displacement, in
minutes, between the primary
and secondary values. The
phase angle of a transformer is
positive when the secondary
value leads the primary value.

Local Settings

This setup allows you to specify your time zone and daylight saving time

options.

To configure the time zone options for your device, select the device site
from the list box on the PAS toolbar, select General Setup from the Meter
Setup menu, and then click on the Local Settings tab.

The available options are described in the following table:

Parameter Options

Default

Description

Country

Default, or country

name

Default Defines

calendar setting. The default

setting stands for the U.S.A.

Daylight saving time Disabled

Enabled

Disabled

When DST is disabled, the RTC

operates in standard time only. When
enabled, the device automatically
updates the time at 2:00 AM at the
pre-defined DST switch dates.

DST start month
DST start week
DST start weekday

Month-week-

weekday
Week = 1

st

, 2

nd

, 3

rd

,

4

th

or Last (last week

of the month)

Second

Sunday in
March

The date when Daylight Saving Time

begins. The DST switch point is
specified by the month, week of the
month and weekday. By default, DST
starts at 2:00 AM on the second
Sunday in March of each year.

DST Start Hour

1-6

2

The hour when Daylight Saving Time

begins.