Chapter 4 PAS Application Software

Configuring Summary Energy and TOU Registers

Series PM172 Powermeters

83

The available options are shown in the following table:

Parameter Options Default

Description

Summary/TOU Registers

TOU Unchecked

Checked

Unchecked Links tariff registers to the selected

energy source

Use Profl

Unchecked
Checked

Unchecked Enables automatic daily profiling for

energy usage registers (both total and
tariff registers if TOU is enabled)

Dmd Profl

Unchecked
Checked

Unchecked Enables automatic daily profiling for

maximum demand registers (both total
and tariff registers if TOU is enabled)

Sum Profl

Unchecked
Checked

Unchecked Enables daily profiling for summary

registers (total of all tariffs)

Units

kWh, kvarh, kVAh,
m3, CF (cubic foot),
CCF (hundred cubic
feet)

None

The register measurement units. When

a register is linked to an internal energy
source, it is set automatically. When an
external pulse source is used, the user
can select a measurement unit for the
register.

Register Source List

Source

Input

None
kWh Import

kWh Export
kvarh Import
kvarh Export
kVAh,
DI1-DI2

None

Links an energy source to the register

Multiplier

0.001 to 100.000

1.000

The multiplication factor for the energy
source.

Target

Reg#1- Reg#8

None

Defines the target billing register for the

energy source. It is set automatically.

Configuring the Daily Tariff Schedule

To configure your daily tariff schedule, select Energy/TOU from the Meter
Setup menu, and then click on the TOU Daily Profiles tab.

The daily profile setup allows you to specify the daily tariff change points with

a 15-minute resolution for 4 seasons using 4 different daily schedules for
each season.

To configure your daily profiles:

1. Select the desired season and day type.

2. Select the start time for each tariff change point and the corresponding

active tariff number.

3. Repeat the setup for all active profiles.

The first tariff change point is fixed at 00:00 hours, and the last tariff change
you specified will be in use until 00:00 hours on the next day.

The energy daily profile log will be automatically configured for the number of
active tariffs you defined in the meter TOU daily profile.