Configuring dnp3, Series pm172 powermeters, Scaling 16-bit ai objects – SATEC RDM172 Manual User Manual

Page 95: Scaling 16-bit binary counters

Advertising
background image

Chapter 4 PAS Application Software

Configuring Communication Protocols

Series PM172 Powermeters

95

Parameter Options Default

Description

Analog Input
Change Event
Object

32-bit -Time
32-bit +Time
16-bit -Time
16-bit +Time

16-bit +Time The default AI change event object

variation for requests with qualifier code
06 when no specific variation is
requested

Binary Counters (BC)

Number of BC
to Generate
events

0-64

3

0

The total number of BC change event
points for monitoring

Binary Counter
Object

32-bit +Flag
32-bit –Flag
16-bit +Flag
16-bit –Flag

32-bit -Flag

The default BC object variation for
requests with qualifier code 06 when no
specific variation is requested

Binary Counter

Change Event
Object

32-bit -Time

32-bit +Time
16-bit -Time
16-bit +Time

32-bit +Time The default BC change event object

variation for requests with qualifier code
06 when no specific variation is
requested

Frozen Binary
Counter Object

32-bit +Flag
32-bit –Flag
32-bit +Time
16-bit +Flag
16-bit –Flag
16-bit +Time

32-bit -Flag

The default frozen BC object variation
for requests with qualifier code 06 when

no specific variation is requested

DNP General Options

16-bit AI
Scaling

Disabled
Enabled

Enabled Allows

scaling 16-bit analog input

objects (see description below)

16-bit BC

Scaling

x1, x10, x100,
x1000

x1

Allows scaling 16-bit binary counter

objects (see description below)

Re-mapping
Event Points

Disabled
Enabled

Disabled

Allows re-mapping event points starting
with point 0.

SBO Timeout

1

2-30 sec

10

Defines the Select Before Operate
(SBO) timeout when using the Control-

Relay-Output-Block object

Time Sync
Period

2

0-86400 sec

86400

Defines the time interval between
periodic time synchronization requests

Multi Fragment
Interval

5-500 ms

50

Defines the time interval between
segments of the response message
when it is fragmented

1

The Select Before Operate command causes the device to start a timer. The following
Operate command must be sent before the specified timeout value expires.

2

The device requests time synchronization by bit 4 in the first octet of the internal
indication word being set to 1 when the time interval specified by the Time Sync
Period elapses. The master should synchronize the time in the device by sending the

Time and Date object to clear this bit. The device does not send time synchronization
requests if the Time Sync Period is set to 0.

3

The total number of AI, BI and BC change event points may not exceed 64. When
you change the number of the change event points in the device, all event
setpoints are set to defaults
(see Configuring DNP Event Classes below).

Scaling 16-bit AI objects

Scaling 16-bit AI objects allows accommodating native 32-bit analog input
readings to 16-bit object format; otherwise it may cause an over-range error

if the full-range value exceeds a 16-bit point limit.

Scaling is enabled by default. It is not applied to points that are read using
32-bit AI objects.

Refer to the PM172 DNP3 Reference Guide for information on the data point

scales and on a reverse conversion that should be applied to the received
scaled values.

Scaling 16-bit Binary Counters

Scaling 16-bit Binary Counters allows changing a counter unit in powers of

10 to accommodate a 32-bit counter value to 16-bit BC object format.