Chapter 3 Display Operations

Menu Operations

46

Series PM172 Powermeters

Label Parameter

Options

Default

Description

Addr

Device address SATEC ASCII: 0-99

Modbus RTU: 1-247
DNP3: 0–65532
DTE: 1-65532
Profibus DP: 0-126

1 (126 for
Profibus)

Device network address

bAud

Baud rate

300-115200 bps

19200 bps The port baud rate

dAtA

Data format and
parity

7E, 8N, 8E

8N

7E data format should
not be used with the
Modbus RTU and DNP3
protocols

H.Sh

Handshaking
(flow control)

nonE=no flow control
SOFt=software
(XON/XOFF)
HArd=hardware (CTS)

None

rtS

RTS mode

nonE = not used

Forc = RTS is
permanently asserted
CtrL = RTS is asserted
during the
transmission

None

1

The meter automatically detects a replaceable communication module and does

not allow you to change the interface, baud rate or data format for the Dial-up
modem, and for the Ethernet or Profibus port.

2

Selecting the DNP3 protocol on the Ethernet port launches the DNP3/TCP server

along with the Modbus/TCP server allowing simultaneous connections on both TCP
ports. Selecting the Modbus protocol for the port disables the DNP3/TCP server.

COM2 Settings

Label Parameter

Options

Default

Description

Prot Communications

protocol

ASCII = SATEC ASCII

rtu = Modbus RTU
dnP3 = DNP3
dtE = DTE

Modbus

RTU

The communications

protocol supported by
the port

rS Port

interface

485 = RS-485
422 = RS-422

RS-485

Addr Device

address

SATEC ASCII: 0-99
Modbus RTU: 1-247
DNP3: 0–65532
DTE: 1-65532

1

Device network address

bAud

Baud rate

300-115200 bps

19200 bps The port baud rate

dAtA

Data format and
parity

7E, 8N, 8E

8N

7E data format should
not be used with the
Modbus RTU and DNP3

protocols

Network Address

This menu allows you to configure the device IP address and the default
gateway address for the Ethernet port. To enter the menu, select “nEt” from
the Main menu, and then press the ENTER button.

To change the IP Address and Default Gateway:

1. To change the device IP address, select the “A” entry in

the upper window with the UP and DOWN arrow buttons.
To change the default gateway address, select the “G”
entry.

2. Press the SELECT button to activate the first address

digit.

3. Use the UP and DOWN arrow buttons to adjust the digit.
4. Press the SELECT button to advance to the next digit.
5. Adjust the remaining address digits.

A.

192.

000.203

168.

G.

192.

000.001

168.