Chapter 4 PAS Application Software

General Meter Setup

64

Series PM172 Powermeters

General Meter Setup

This section describes how to configure the PM172 for your particular

environment and application using PAS.

Basic Meter Setup

Before operating your meter, provide the device with basic information about

your electrical network.

To enter the Setup dialog, select the device site from the list box on the PAS
toolbar, and then select General Setup from the Meter Setup menu.

The following table lists available device configuration options.

Parameter Options

Default

Description

Basic Configuration

Wiring mode

See Table below

4LN3

The wiring connection of the device

PT ratio

1

1.0-6500.0

1.0

The phase potential transformer’s
primary to secondary ratio

PT Ratio multiplier

Ч1, Ч10

Ч1

PT Ratio multiplication factor. Used in
extra high voltage networks to
accommodate the PT ratio for 500 kV

and higher networks.

CT primary current 1-20,000 A

5 A

The primary rating of the phase
current transformer

Nominal voltage

EH

10-690 V

120 V

The nominal secondary line-to-neutral
or line-to-line voltage. Used as a

reference voltage for the disturbance
monitor.

Maximum demand
load current

0-20,000 A

0

The maximum demand load current
(0 = CT primary current)

Nominal frequency 50,60,25,400 Hz

60 Hz

The nominal line frequency