Device options – SATEC RDM172 Manual User Manual

Page 43

Advertising
background image

Chapter 3 Display Operations

Menu Operations

Series PM172 Powermeters

43

Label Parameter Options

Default

Description

ConF Wiring

connection

(configuration) mode

See “Basic
Meter
Setup” in
Chapter 4

4Ln3

The wiring connection of the
device

Pt

PT ratio

1.0-6500.0 1.0

The phase potential

transformer’s primary to
secondary ratio

Pt.F

PT Ratio multiplier

Ч1, Ч10

Ч1

PT Ratio multiplication factor.
Used in extra high voltage
networks to accommodate the
PT ratio for 500 kV and higher
networks.

U.SEC Nominal

secondary

voltage

EH

10-690 V

120 V

The nominal secondary line-to-

neutral or line-to-line voltage.
Used as a reference voltage for
the disturbance monitor.

Ct

CT primary current

1-20,000 A 5 A

The primary rating of the phase
current transformer

d.P

Power block demand
period

E

1, 2, 3, 5,

10, 15, 20,
30, 60 min,
E=external
sync

15 min

The length of the demand

period for power demand
calculations. If the external
synchronization is selected, a
pulse front on the digital input
DI1 denotes the start of the
demand interval.

nd.P

The number of blocks in
the sliding window

E

1-15

1

The number of blocks to be

averaged for sliding window
demands

Ad.P

Ampere, volt and THD
demand period

0-1800 sec 900 sec

The length of the demand
period for ampere, volt and
THD demand calculations

Freq Nominal

frequency 50,60,25,

400 Hz

60 Hz

The nominal line frequency

LoAd

Maximum demand load

current

0-20,000 A 0

The maximum demand load

current (0 = CT primary)

Ì

Always specify the wiring mode and transformer ratings prior to setting up

setpoints and analog outputs.

Ì

The maximum value for the product of the phase CT primary current and PT ratio

is 57,500,000. If the product is greater, power readings are zeroed.

Device Options

This menu allows you to change the user-configurable device options or put
the meter into energy test mode. To enter the menu, select the “OPtS” entry

from the Main menu, and then press the ENTER button.

To select a setup option:

1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to scroll to the

desired option.

To change the option:

1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the

desired option.

3. Press ENTER to confirm your changes and to store your

new setting, or press ESC to discard changes.

To exit the menu, press ESC.

OPtS

rEAc

P.cAL

Advertising