Chapter 3 Display Operations

Menu Operations

Series PM172 Powermeters

53

The following table lists available options.

Label Parameter Options

Default

Description

UPdt

Display update rate 0.1-10.0 sec 1 sec

Defines the interval between
display updates

ScrL

Auto scroll interval

None,
2-15 sec

None

Defines the scroll interval for

the main data display or
disables auto scroll

rEtn

Auto return to the
main screen

diS =
disabled,
En =
Enabled

Enabled

Enables automatic return to
the main display if no buttons
are pressed for 5 minutes

bAr

Reference load
current for LED bar
graph

0-20,000A
(0 = CT
primary
current)

0

Defines the nominal load
(100%) level for the bar
graph display

Uolt Primary/Secondary

volts units

Pri, SEc

Primary

Selects primary or secondary
units for volts display

Ph.P Phase

powers

display mode

diS, En

Disabled

Disables or enables phase

powers in the main display

Fund. Fundamental

component display
mode

diS, En

Disabled

Disables or enables
fundamental values in the
main display

dAtE

Date order

dnY, ndY,

Ynd
(d=day,
n=month,
y=year)

mm.dd.yy Defines the date order in the

RTC display

rSt

Simple reset mode

PASS =
password
required
En =
enabled

PASS

PASS = the simple reset is not
allowed when password
protection is enabled
En = enables the simple reset
buttons regardless of
password protection

SoFt. Display

firmware

version

N/A

N/A

Shows display firmware

version, like 1.2.8

SoFt. Device

firmware

version

N/A

N/A

Shows device firmware
version, like 15.01.09

Meter Security

The Access Control menu allows you to change the user password and

enable or disable password protection. To enter the menu, select the “AccS”
entry from the main menu and press the ENTER button.

The password in your meter is preset to 0 at the factory, and password
protection is disabled.

To change the password:

1. Select the “PASS” entry in the upper window with the UP

and DOWN arrow buttons.

2. Press the SELECT button to activate the first password

digit.

3. Use the UP and DOWN arrow buttons to adjust the digit.
4. Press the SELECT button to advance to the next digit.
5. Adjust the remaining password digits.
6. Press ENTER to confirm your new password.

Ì

Your new password is effective for both the display and communication ports.

To enable or disable password protection:

PASS

0000

AccS

ESC