Chapter 3 Display Operations

Menu Operations

Series PM172 Powermeters

49

Use the UP and DOWN arrow buttons to scroll to the desired setpoint.


To select a setpoint parameter:

1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to scroll to the

desired parameter.

To change the parameter value:

1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the

desired value.

3. Press ENTER to confirm the new parameter setting, or

press ESC to discard changes.

4. You are returned to the middle window to select and

configure another parameter, or confirm the setpoint
settings and exit the menu.

To store your new setpoint settings after you configured all setpoint
parameters:

1. When the middle window is highlighted, press the ENTER

button.

2. You are returned to the upper window to select another

setpoint or exit the menu.

To exit the menu, press ESC.

The following table lists available setpoint options. For a list of available

setpoint triggers and actions, see “Using Control Setpoints” in Chapter 4.

Label Parameter Options

Description

LGC.2-

LGC.4

Logical operator OR, AND

Combines setpoint triggers in a

logical expression

TrG.1-TrG.4 Trigger

parameter #1-
#4

See
Appendix C

The analog or digital value that is

used as an argument in a logical
expression

On.1-On.4 Operate

limit

The threshold (in primary units) at
which the conditional expression
would be evaluated to true. Not
applicable for digital triggers.

OFF.1-
OFF.4

Release limit

The threshold (in primary units) at
which the conditional expression
would be evaluated to false. Defines
the hysteresis for analog triggers.
Not applicable for digital triggers.

Act.1-Act.4 Setpoint

action

#1-#4

See
Appendix C

The action performed when the

setpoint expression is evaluated to
true (the setpoint is in operated
state)

On d

Operate delay

0-999.9 sec The time delay before operation

when the operate conditions are
fulfilled

OFF d

Release delay

0-999.9 sec The time delay before release when

the release conditions are fulfilled

Analog Inputs Setup

This entry appears only if the meter is ordered with optional analog inputs.
For more information on configuring analog inputs in your meter, see

“Programming Analog Inputs” in Chapter 4.

To enter the menu, select the “A.In.1” or “A.In.2” entry from the Main menu
for the AI1 and AI2 input respectively, and press the ENTER button.

SP.1

rtHi.C1

trG.1

SP.1

200

On.1

SP.1

180

OFF.1

SP.1

Or

LOG.2

SEtP

rEL.1

Act.1

SP.1

rtHi.C2

trG.2

SP.1

200

On.2

SP.1

180

OFF.2