Chapter 4 PAS Application Software

General Meter Setup

78

Series PM172 Powermeters

The meter provides 16 control setpoints with programmable operate and

release delays. Each setpoint evaluates a logical expression with up to four
arguments using OR/AND logic. Whenever an expression is evaluated as
“true”, the setpoint performs up to four concurrent actions that can send a
command to the output relays, increment or decrement a counter, or trigger a
recorder.

The logical controller provides very fast response to events. The scan time
for all setpoints is 1 cycle time (16.6 ms at 60Hz and 20 ms at 50/400 Hz).

To program the setpoints, select General Setup from the Meter Setup menu,
and then click on the Control/Alarm Setpoints tab.

The available setpoint options are described in the following table.

Option Range

Description

Triggers

OR/AND

OR, AND

The logical operator for the trigger

Trigger
parameter

See Appendix C The trigger parameter that is used as an argument in

the logical expression

Operate limit

The threshold (in primary units) at which the

conditional expression would be evaluated to true.
Not applicable for digital triggers.

Release limit

The threshold (in primary units) at which the
conditional expression would be evaluated to false.
Defines the hysteresis for analog triggers. Not
applicable for digital triggers.

Actions

Action

See Appendix C The action performed when the setpoint expression is

evaluated to true (the setpoint is in operated state)

Delays

Operate delay 0.1-999.9 sec

The time delay before operation when the operate

conditions are fulfilled

Release delay 0.1-999.9 sec

The time delay before release when the release
conditions are fulfilled