Communication ports, Com1 settings – SATEC RDM172 Manual User Manual

Page 45

Advertising
background image

Chapter 3 Display Operations

Menu Operations

Series PM172 Powermeters

45

Label Parameter

Options

Default

Description

U1.rt
U2.rt
U3.rt

V1-V3 voltage
transformer
ratio correction
factor

0.900 to 1.100

1.000

The ratio of the true
transformer ratio to the
marked ratio.

U1.AG

U2.AG
U3.AG

V1-V3

transformer
phase angle
error, minutes

-600 to 600
(-2700 to 2700 with
V13.7X.XX)

0 The

phase

displacement, in
minutes, between the
primary and secondary
values. The phase angle
of a voltage transformer
is positive when the
secondary value leads
the primary value.

C1.rt
C2.rt

C3.rt

I1-I3 current
transformer

ratio correction
factor

0.900 to 1.100

1.000

The ratio of the true
transformer ratio to the

marked ratio.

C1.AG
C2.AC
C3.AG

I1-I3
transformer
phase angle
error, minutes

-600 to 600
(-2700 to 2700 with
V13.7X.XX)

0 The

phase

displacement, in
minutes, between the
primary and secondary
values. The phase angle
of a current transformer
is positive when the
secondary value leads
the primary value.

Communication Ports

These two menus allow you to configure parameters for communication
ports COM1 and COM2. To enter the menu, select “Prt.1” for COM1 or
“Prt.2” for COM2 from the Main menu, and then press the ENTER button.

To select a setup option:

1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to scroll to the

desired option.

To change the option:

1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the

desired option.

3. Press ENTER to confirm your changes and to store your

new setting, or press ESC to discard changes.

To exit the menu, press ESC.

The following tables list available port options.

COM1 Settings

Label Parameter

Options

Default

Description

Prot Communications

protocol

ASCII = SATEC ASCII
rtu = Modbus RTU

2

dnP3 = DNP3

2

dtE = DTE
PrFb = Profibus DP

Modbus
RTU

The communications
protocol supported by
the port

rS

Port interface

1

232 = RS-232

485 = RS-485
422 = RS-422
dial = Dial-up Modem
Eth.= Ethernet
PrFb = Profibus DP

Depends

on the
order

For non-serial interfaces

- not changeable;
automatically detected
by the meter

Prt.1

rtu

Prot