Minimum mounting clearances, Figure 1 – Rockwell Automation 20D PowerFlex 700S Phase II Drive Frames 1...6 Installation Instructions User Manual

Page 15

Advertising
background image

Rockwell Automation Publication 20D-IN024C-EN-P - July 2013

15

PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control

Minimum Mounting Clearances

Specified vertical clearance requirements are intended to be from the drive to the
closest object that can restrict airflow through the drive heat sink and chassis. The
drive must be mounted in a vertical orientation as shown, and must make full
contact with the mounting surface. Do not use standoffs or spacers. In addition,
inlet air temperature must not exceed the product specification. See

Table 8

on

page

14

for ambient air temperature limits.

Figure 1 - Minimum Mounting Clearance Requirements

IMPORTANT

PowerFlex 700S drives must be mounted in a clean, dry location. Contaminants
such as oils, corrosive vapors and abrasive debris must be kept out of the
enclosure. These enclosures are intended for indoor use primarily to provide a
degree of protection against contact with enclosed equipment. These
enclosures offer no protection against airborne contaminants.

50.8 mm

(2.0 in.)

101.6 mm (4.0 in.)

101.6 mm (4.0 in.)

101.6 mm (4.0 in.)

101.6 mm (4.0 in.)

101.6 mm (4.0 in.)

101.6 mm (4.0 in.)

With Adhesive

Label Removed

Adhesive Label

With Adhesive Label

Left in Place

Air flow through the drive

must not be impeded.