Rockwell Automation Publication 20D-IN024C-EN-P - July 2013

PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control

Fram

e

Vo

lt

ag

e

Code

Current

Ra

ti

ng

Factory Default Jumper Settings

Power Source Type

MOV/Input Filter
Caps

(1) (2)

DC Bus Common
Mode Caps

5

C
F
W

052
060
140

Two green/yellow
wires connected to
the Power Terminal
Block rail

Green/yellow wire to
CM Cap Board is
connected to ground

Solid Ground
1. CM Cap jumper wire should be connected to ground

with a metal screw. Verify. If necessary, remove the
nylon screw/spacer and insert a metal M5 x 8 screw.
Torque to 3.2 N•m (28 lb•in).

2. MOV/Input Filter Cap jumper wires should be

connected to ground with a metal screw. Verify. If
necessary, remove the nylon screw/spacer and insert
a metal M5 x 12 screw.

Non-Solid Ground
1. CM Cap jumper wire should be insulated from ground

with a nylon screw/spacer. Verify. If necessary,
remove the metal screw and insert a M5 x 15 nylon
screw/spacer.

2. MOV/Input Filter Cap jumper wires should be

insulated from ground with a nylon screw/spacer.
Verify. If necessary, remove the metal screw and
insert a
M5 x 20 nylon screw/spacer.

E
F
T
W

077
082
098
099

Two green/yellow
wires connected to
chassis ground

Green/yellow wire to
CM Cap Board is
connected to ground

Solid Ground
1. CM Cap jumper wire should be connected to ground

with a metal screw. Verify. If necessary, remove the
nylon screw/spacer and insert a metal M5 x 8 screw.
Torque to 3.2 N•m (28 lb•in).

2. MOV jumper wire should be connected to ground

with metal screws. Verify. If necessary, remove the
nylon screw/spacers and insert metal M5 x 12 screws.

3. Input Filter Cap jumper wire should be connected to

ground with a metal screw. Verify. If necessary,
remove the nylon screw/spacer and insert metal M5
x 8 screw.

Non-Solid Ground
1. CM Cap jumper wire should be insulated from ground

with a nylon screw/spacer. Verify. If necessary,
remove the metal screw and insert a M5 x 15 nylon
screw/spacer.

2. MOV jumper wire should be insulated from ground

with a nylon screw/spacer. Verify. If necessary,
remove the metal screws and insert a M5 x 20 nylon
screw/spacer.

3. Input Filter Cap jumper wire should be insulated from

ground with a nylon screw/spacer. Verify. If
necessary, remove the metal screws and insert a M5 x
15 nylon screw/spacer.

(1) AC input drives only. MOV’s and input filter caps do not exist on DC input drives.
(2) When removing MOV’s, the input filter capacitor must also be removed.

WIRE RANGE: 14-1/0 AWG (2.5-35 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY

POWER TERMINAL RATINGS

WIRE RANGE: 6-1/0 AWG (16-35 MM2)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)

GROUND TERMINAL RATINGS (PE)

300 VDC EXT PWR SPLY TERM (PS+, PS-)

WIRE RANGE: 22-10 AWG (0.5-4 MM2)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)

17

21

INPUT AC

OUTPUT

Optional

Communications

Module

9

CM Cap

MOV

MOV / Input Filter Cap

WIRE RANGE: 14-1/0 AWG (2.5-35 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY

POWER TERMINAL RATINGS

WIRE RANGE: 6-1/0 AWG (16-35 MM2)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)

GROUND TERMINAL RATINGS (PE)

300 VDC EXT PWR SPLY TERM (PS+, PS-)

WIRE RANGE: 22-10 AWG (0.5-4 MM2)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)

17

21

INPUT AC

OUTPUT

Optional

Communications

Module

9

PE

CM Cap

MOV

MOV

Input Filter
Cap