background image

Rockwell Automation Publication 20D-IN024C-EN-P - July 2013

31

PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control

Fr

am

e

Vo

lt

ag

e

Co

de

Current

Ra

ti

ng

Factory Default Jumper Settings

Power Source Type

MOV/Input Filter
Caps

(1) (2)

DC Bus Common
Mode Caps

5

B
C
D
H
J
N
P
R

All,
except
C140
(see
next
page)

Two green/yellow
wires connected to
the Power Terminal
Block rail

Green/yellow wire is
connected to ground

Solid Ground
1. CM Cap jumper wire should be connected to

ground with a metal screw. Verify.
Newer Drives - If necessary, remove the nylon

screw/spacer and insert a metal M5 x 8 screw.
Torque to 3.2 N•m (28 lb•in).

Older Drives - Remove the I/O Cassette (see

Installation Instructions for details). The green/
yellow CM Cap jumper wire is located on the
back of chassis and should be connected to
ground with a metal screw. If necessary, remove
the insulation from the wire terminal and
connect to chassis with a metal M5 x 12 screw.
Torque screw to 3.2 N•m (28 lb•in).

2. MOV/Input Filter Cap jumper wires should be

connected to ground with a metal screw. Verify. If
necessary, remove the nylon screw/spacer and
insert a metal M5 x 12 screw.

Non-Solid Ground
1. CM Cap jumper wire should be insulated from

ground. Verify.
Newer Drives - If necessary, remove the metal

screw and insert a M5 x 15 nylon screw/spacer.

Older Drives - Remove the I/O Cassette (see

Installation Instructions for details). If
necessary, insulate/secure jumper wire to guard
against unintentional contact with chassis or
components.

2. MOV/Input Filter Cap jumper wires should be

insulated from ground with a nylon screw/spacer.
Verify. If necessary, remove the metal screw and
insert a M5 x 20 nylon screw/spacer.

(1) AC input drives only. MOV’s and input filter caps do not exist on DC input drives.
(2) When removing MOV’s, the input filter capacitor must also be removed.

WIRE RANGE: 14-1/0 AWG (2.5-35 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY

POWER TERMINAL RATINGS

WIRE RANGE: 6-1/0 AWG (16-35 MM2)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)

GROUND TERMINAL RATINGS (PE)

300 VDC EXT PWR SPLY TERM (PS+, PS-)

WIRE RANGE: 22-10 AWG (0.5-4 MM2)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)

17

21

INPUT AC

OUTPUT

Optional

Communications

Module

9

CM Cap -
Older Drives

MOV / Input Filter Cap

MOV

CM Cap - Newer Drives