Rockwell Automation Publication 20D-IN024C-EN-P - July 2013

51

PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control

Table 21 - 810 Volt DC Input Frames 1…6 Drive Protection Devices

Table 22 - 932Volt DC Input Frames 5 & 6 Drive Protection Devices

20DJ180

(1)

6

150

198

400

HSJ400

125

171.2

400

HSJ400

20DJ248

(1)

6

200

272

400

HSJ400

150

198

400

HSJ400

(1) Also applies to “R” voltage class. s must be applied in the (+) leg and (-) leg of the DC Common Bus.
(2) The power source to Common Bus inverters must be derived from AC Voltages 600V or less, as defined in NFPA70; Art 430-18 (NEC).

Battery supplies or MG sets are not included. The following devices were validated to break current of the derived power DC Bus:
Disconnects: Allen-Bradley Bulletin No. 1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. s:
Bussmann Type JKS, all sizes; Type 170M, Case Sizes 1, 2 and 3, or Ferraz Shawmut Type HSJ, all sizes. For any other devices, please
contact the factory.

Drive Cat. No.

Frame HP Rating

DC Input Ratings

Fuse

Non-Time Delay

(1)

(1) The power source to Common Bus inverters must be derived from AC Voltages 600V or less, as defined in NFPA70; Art 430-18 (NEC).

Battery supplies or MG sets are not included. The following devices were validated to break current of the derived power DC Bus:
Disconnects: Allen-Bradley Bulletin No. 1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. s:
Bussmann Type JKS, all sizes; Type 170M, Case Sizes 1, 2 and 3, or Ferraz Shawmut Type HSJ, all sizes. For any other devices, please
contact the factory.

ND

HD

Amps

20DE1P7

1

1

0.75 1.5

3

JKS-3

20DE2P7

1

2

1.5

2.4

6

JKS-6

20DE3P9

1

3

2

3.5

6

JKS-6

20DE6P1

1

5

3

6.2

10

JKS-10

20DE9P0

1

7.5

5

9.1

15

HSJ15

20DE011

1

10

7.5

11.5

20

HSJ20

20DE017

1

15

10

18

30

HSJ30

20DE022

2

20

15

23.6

40

HSJ40

20DE027

2

25

20

29

50

HSJ50

20DE032

3

30

25

34.3

60

HSJ60

20DE041

3

40

30

43.9

70

HSJ70

20DE052

3

50

40

55.7

90

HSJ90

20DE062

4

60

50

68.0

125

HSJ125

20DT099

5

100

108.6

150

HSJ150

75

84.5

150

HSJ150

20DT144

6

150

158

200

HSJ200

125

137.1

200

HSJ200

Drive Cat. No.

Frame kW Rating

DC Input Ratings

Fuse

Non-Time Delay

(1)

(1) The power source to Common Bus inverters must be derived from AC Voltages 600V or less, as defined in NFPA70; Art 430-18 (NEC).

Battery supplies or MG sets are not included. The following devices were validated to break current of the derived power DC Bus:
Disconnects: Allen-Bradley Bulletin No. 1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. s:
Bussmann Type JKS, all sizes; Type 170M, Case Sizes 1, 2 and 3, or Ferraz Shawmut Type HSJ, all sizes. For any other devices, please
contact the factory.

ND

HD

Amps

20DW098

5

90

92.3

160

HSJ160

75

92.3

160

HSJ160

20DW142

6

132

162.2

250

HSJ250

110

134.9

250

HSJ250

Drive Cat. No.

Frame

HP Rating

DC Input Ratings

Fuse

Non-Time Delay

(2)

ND

HD

Amps