Step 5: control and i/o wiring, Control and i/o wiring recommendations – Rockwell Automation 20D PowerFlex 700S Phase II Drive Frames 1...6 Installation Instructions User Manual

Page 52

Advertising
background image

52

Rockwell Automation Publication 20D-IN024C-EN-P - July 2013

PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control

Step 5: Control and I/O
Wiring

Important points to remember about control and I/O wiring:

Always use copper wire.
Wire with an insulation rating of 600V or greater is recommended.
Control and signal wires should be separated from power wires by at least

0.3 meters (1 foot).

For CE compliance, 115 volt digital input wiring must be shielded or must

not exceed 30 meters (98 feet) in length.

To maintain electrical safety for all user-accessible low voltage circuits

(SELV and PELV circuits), I/O terminals designated for 24V or lower
voltage must not be connected to a circuit of higher voltage or a circuit
that is not adequately insulated from dangerous voltages with double or
reinforced insulation within other connected equipment or wiring.

To provide electrical safety for user-accessible low voltage I/O circuits that

are referenced to earth (PELV circuits) and that may be touched
simultaneously, care should be taken to provide a common earth reference
for all equipment connected to the drive.

Control and I/O Wiring Recommendations

IMPORTANT

I/O terminals labeled “(–)” or “Common” are not referenced to earth ground
and are designed to greatly reduce common mode interference. Grounding
these terminals can cause signal noise.

ATTENTION: Hazard of personal injury or equipment damage exists when
using bipolar input sources. Noise and drift in sensitive input circuits can cause
unpredictable changes in motor speed and direction. Use speed command
parameters to help reduce input source sensitivity.

Type

Wire Type(s)

Description

Min Insulation Rating

Signal

(1) (1) (2)

Standard Analog I/O

0.750 mm

2

(18AWG), twisted pair, 100% shield with drain.

300V,
75…90 °C (167…194 °F)

Remote Pot

0.750 mm

2

(18AWG), 3 conductor, shielded.

Encoder/
Pulse I/O
<30 m (100 ft)

Combined

0.196 mm

2

(24AWG), individually shielded pairs.

Encoder/
Pulse I/O
30 to 152 m
(100 to 500 ft)

Signal

0.196 mm

2

(24AWG), individually shielded pairs.

Power

0.750 mm

2

(18AWG) in.dividually shielded pairs

Combined

0.330 mm

2

(22AWG), power is 0.500 mm

2

(20AWG) individually

shielded pairs.

Encoder/
Pulse I/O
152 to 259 m
(500 to 850 ft)

Signal

0.196 mm

2

(24AWG), individually shielded pairs.

Power

0.750 mm

2

(18AWG) individually shielded pairs.

Combined

0.750 mm

2

(18AWG) individually shielded pairs.

Digital I/O
Safety Inputs
Homing Inputs

(1)

Un-shielded

Per US NEC or applicable national or local code.

300V,
60 °C (140 °F)

Shielded

Multi-conductor shielded cable

0.750 mm

2

(18AWG), 3 conductor, shielded.

(1) If the wires are short and contained within a cabinet that has no sensitive circuits, the use of shielded wire may not be necessary, but is always recommended.
(2) I/O terminals labeled “(–)” or “Common” are not referenced to earth ground and are designed to greatly reduce common mode interference. Grounding these terminals can cause signal noise.

Advertising