Second encoder feedback option – Rockwell Automation 20D PowerFlex 700S Phase II Drive Frames 1...6 Installation Instructions User Manual

Page 62

Advertising
background image

62

Rockwell Automation Publication 20D-IN024C-EN-P - July 2013

PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control

Second Encoder Feedback Option

Second Encoder Feedback Option Specifications

Recommended Cables for the Second Encoder Feedback Option Card

Second Encoder Feedback Option Terminal Designations

Consideration

Description

Input

Dual Channel Plus Marker, Isolated with differential transmitter Output (Line Drive)
Incremental, Dual Channel Quadrature type

Encoder Voltage Supply

5V DC or 12V DC 320 mA per channel
5V DC requires an external power supply.
12 V DC minimum high state voltage of 7V DC, maximum low state voltage of 0.4V DC

Maximum Input Frequency

400 kHz

Cable Type and Length

Wire Type(s)

Description

Encoder/Pulse I/O
Less 30.5 m (100 ft)

Combined:

Belden 9730 (or equivalent)

(1)

(1) Belden 9730 is 3 individually shielded pairs (2 channel plus power). If 3 channel is required, use Belden 9728 (or equivalent).

0.196 mm

2

(24AWG),

individually shielded.

Encoder/Pulse I/O
30.5 m (100 ft) to 152.4 m (500
ft)

Signal:

Belden 9730/9728 (or equivalent)

(1)

0.196 mm

2

(24AWG),

individually shielded.

Power:

Belden 8790

(2)

(2) Belden 8790 is 1 shielded pair.

0.750 mm

2

(18AWG)

Combined:

Belden 9892

(3)

(3) Belden 9892 is 3 individually shielded pairs (3 channel), 0.33 mm

2

(22 AWG) plus 1 shielded pair 0.5 mm

2

(20 AWG) for power.

0.330 mm

2

or 0.500 mm

2 (3)

Encoder/Pulse I/O
152.4 m (500 ft) to 259.1 m (850
ft)

Signal:

Belden 9730/9728 (or equivalent)

(1)

0.196 mm

2

(24AWG),

individually shielded.

Power: Belden

8790

(2)

0.750 mm

2

(18AWG)

Combined:

Belden 9773/9774 (or equivalent)

(4)

(4) Belden 9773 is 3 individually shielded pairs (2 channel plus power). If 3 channel is required, use Belden 9774 (or equivalent).

0.750 mm

2

(18AWG),

individually shielded pair.

Term. No.

Signal

Description

1…4

Not connected.
Refer to DriveGuard® Safe Torque Off with Second
Encoder Option on
page

61

.

5

A

Quadrature A input

6

Not A

7

B

Quadrature B input

8

Not B

9

Z

Marker Pulse

10

Not Z

11

Power

DC Power for encoder interface

12

Common

13

Shield

Connection point for encoder cable shield