PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control

Figure 17 - Main Control Board Dip Switches

Hardware Enable Circuitry

By default, digital input 6 is configured for hardware enable input. This is for
applications requiring the drive to be disabled

without software interpretation.

With the “HW Enable Jumper (Shunt)” on the pins closest to the circuit board
(2-4), digital input 6 is configured as a “dedicated” hardware enable. If this
configuration is not required, the “HW Enable Jumper (Shunt)” may be moved
to the out board pins (1-3), making digital input 6 user programmable via
parameter 830 [Dig In6 Sel]. See

Figure 17

on page

54

.

1 2

FRONT

TOP VIEW

SIDE VIEW

Up = Open = Off

Down = Closed = On

SWITCH S5

FRONT

TOP VIEW

SIDE VIEW

Up = Open = Off

Down = Closed = On

SWITCH S2

1 2

3 4

1 2

FRONT

TOP VIEW

SIDE VIEW

Up = Open = Off

Down = Closed = On

SWITCH S3

1 2

FRONT

TOP VIEW

SIDE VIEW

Up = Open = Off

Down = Closed = On

SWITCH S4

= HW Enable

= No HW Enable

JUMPER P22

1

2

3

4

1

2

3

4

16

15

JUMPER P13

= Gate Enabled

16

15

= Gate Disabled

SWITCH S1

RUN

PROG

REMOTE

Up

Down

Center