Jumper installation, removal and storage, Insulating jumper wires, Drive identification – Rockwell Automation 20D PowerFlex 700S Phase II Drive Frames 1...6 Installation Instructions User Manual

Page 28

Advertising
background image

28

Rockwell Automation Publication 20D-IN024C-EN-P - July 2013

PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control

To connect or disconnect these devices, refer to pages 29 through 32.

In addition, on an ungrounded distribution system where the line-to-ground
voltages on any phase could exceed 125% of the nominal line-to-line voltage, an
isolation transformer should be installed. See Wiring and Grounding Guidelines
for PWM AC Drives, publication

DRIVES-IN001

for more information on

impedance grounded and ungrounded systems.

Jumper Installation, Removal and Storage

PowerFlex 700S drives utilize plug-in style jumpers and jumper wires. Most drives
will have a jumper storage area inside the front cover. Extra jumpers or jumpers
that have been removed should be stored in this location for use at a later time.

Insulating Jumper Wires

Some drives utilize nylon screws and spacers to insulate jumper
wires from ground and secure them to the chassis. The
components must be installed as shown.

Drive Identification

Refer to the drive nameplate and locate the “Voltage Code,” “Current Rating,”
“Frame,” and “Series”. Use this information to locate the proper procedure in the
following tables.

IMPORTANT

Common mode capacitors are required to conform with the EMC directive.
Removing these devices will withdraw the associated directive.

Cat No. 20D

D xxx

x x xxxxxxx

Made in the USA (TAC 1J)
Rockwell Automation, Mequon WI 53092-4400

UL TYPE 1/IP20

Mfd. in 2007 on Aug 1

Frame:

3

Serial Number: xxxxxxx

Series:

B

Original Firmware V. x.xxx

Listed

Ind. Cont
Eq. 966X

U

c

US

L

®

Normal Duty Power
Heavy Duty Power

AC Voltage Range
Amps

Input: 3 Phase, 47-63Hz

Output: 3 Phase, 0-400 Hz

AC Voltage Range
Base Hz (default)
Continuous Amps
1 Min Overload Amps
3 Sec Overload Amps

xxx kW
xxx kW

342-440

xxx

0-400
50 Hz

xxx
xxx
xxx

xxx kW
xxx kW

432-528

xxx

400V

480V

0-460
60 Hz

xxx
xxx
xxx

N223

Voltage Code

Frame

Current Rating

Series

Advertising
This manual is related to the following products: