Step 1: read the general precautions, Qualified personnel, Personal safety – Rockwell Automation 20D PowerFlex 700S Phase II Drive Frames 1...6 Installation Instructions User Manual

Page 6: Qualified personnel personal safety

Advertising
background image

6

Rockwell Automation Publication 20D-IN024C-EN-P - July 2013

PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control

Step 1: Read the General
Precautions

Qualified Personnel

Personal Safety

ATTENTION: Only qualified personnel familiar with adjustable frequency AC drives and associated machinery should plan or
implement the installation, startup and subsequent maintenance of the system. Failure to comply may result in personal injury
and/or equipment damage.

ATTENTION: To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged before performing any
work on the drive. Measure the DC bus voltage at the +DC and –DC terminals of the Power Terminal Block (refer to page

40

for

location). The voltage must be zero.

ATTENTION: Hazard of personal injury or equipment damage exists when using bipolar input sources. Noise and drift in sensitive
input circuits can cause unpredictable changes in motor speed and direction. Use speed command parameters to help reduce input
source sensitivity.

ATTENTION: Risk of injury or equipment damage exists. DPI or SCANport host products must not be directly connected together
via 1202 cables. Unpredictable behavior can result if two or more devices are connected in this manner.

ATTENTION: The drive start/stop/enable control circuitry includes solid state components. If hazards due to accidental contact
with moving machinery or unintentional flow of liquid, gas or solids exists, an additional hardwired stop circuit may be required to
remove the AC line to the drive. An auxiliary braking method may be required.

ATTENTION: Hazard of personal injury or equipment damage due to unexpected machine operation exists if the drive is
configured to automatically issue a Start or Run command. Do not use these functions without considering applicable local,
national and international codes, standards, regulations or industry guidelines.

ATTENTION: Parameters 365 [Encdr0 Loss Cnfg] - 394 [VoltFdbkLossCnfg] let you determine the action of the drive in response to
operating anomalies. Precautions should be taken to be sure that the settings of these parameters do not create hazards of
personal injury or equipment damage.

ATTENTION: Parameters 383 [SL CommLoss Data] - 392 [NetLoss DPI Cnfg] let you determine the action of the drive if
communications are disrupted. You can set these parameters so the drive continues to run. Precautions should be taken to ensure
the settings of these parameters do not create hazards of personal injury or equipment damage.

ATTENTION: This product contains a 3V Lithium battery if the DriveLogix Controller option board is installed. Perchlorate Material -
special handling may apply.
See

www.dtsc.ca.gov/hazardouswaste/perchlorate

Advertising