Table 19 - 540 Volt DC Input Frames 1…6 Drive Protection Devices

Table 20 - 650 Volt DC Input Frames 1…6 Drive Protection Devices

Drive Cat. No.

Frame kW Rating

DC Input Ratings

Fuse

Non-Time Delay

(2)

(2) The power source to Common Bus inverters must be derived from AC voltages 600V or less, as defined in NFPA70; Art 430-18 (NEC).

Battery supplies or MG sets are not included. The following devices were validated to break current of the derived power DC Bus:
Disconnects: Allen-Bradley Bulletin No. 1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. s:
Bussmann Type JKS, all sizes; Type 170M, Case Sizes 1, 2 and 3, or Ferraz Shawmut Type HSJ, all sizes. For any other devices, please
contact the factory.

ND

HD

Amps

20DC3P5

1

1.5

1.1

3.7

8

JKS-8

20DC5P0

1

2.2

1.5

5.3

10

JKS-10

20DC8P7

1

4

3.0

9.3

15

HSJ15

20DC011

1

5.5

4

12.6

20

HSJ20

20DC015

1

7.5

5.5

16.8

25

HSJ25

20DC022

1

11

7.5

24

40

HSJ40

20DC030

2

15

11

33.2

50

HSJ50

20DC037

2

18.5

15

40.9

70

HSJ70

20DC043

3

22

18.5

47.5

90

HSJ90

20DC056

3

30

22

61.9

100

HSJ100

20DC072

3

37

30

80.5

125

HSJ125

20DC085

4

45

37

95.1

150

HSJ150

20DH105

(1)

(1) Also applies to “P” voltage class. s must be applied in the (+) leg and (-) leg of the DC Common Bus.

5

55

120.2

175

HSJ175

45

95.1

175

HSJ175

20DH125

(1)

5

55

120.2

200

HSJ200

45

95.1

200

HSJ200

20DH140

5

75

159

250

HSJ250

55

120.2

250

HSJ250

20DH170

(1)

6

90

192

350

HSJ350

75

159

350

HSJ350

20DH205

(1)

6

110

226

350

HSJ350

90

192

350

HSJ350

20DH260

(1)

6

132

298

400

HSJ400

110

226

400

HSJ400

Drive Cat. No.

Frame

HP Rating

DC Input Ratings

Fuse

Non-Time Delay

(2)

ND

HD

Amps

20DD2P1

1

1

0.75

1.9

6

JKS-6

20DD3P4

1

2

1.5

3.0

6

JKS-6

20DD5P0

1

3

2

4.5

10

JKS-10

20DD8P0

1

5

3

8.1

15

HSJ15

20DD011

1

7.5

5

11.1

20

HSJ20

20DD014

1

10

7.5

14.6

30

HSJ30

20DD022

1

15

10

23.3

40

HSJ40

20DD027

2

20

15

28.9

50

HSJ50

20DD034

2

25

20

36.4

60

HSJ60

20DD040

3

30

25

42.9

80

HSJ80

20DD052

3

40

30

55.7

90

HSJ90

20DD065

3

50

40

69.6

100

HSJ100

20DD077

4

60

50

84.5

150

HSJ150

20DJ096

(1)

5

75

105.3

175

HSJ175

60

84.5

175

HSJ175

20DJ125

(1)

5

100

137.1

200

HSJ200

75

105.3

200

HSJ200

20DJ156

(1)

6

125

171

300

HSJ300

100

137.1

300

HSJ300